CMC-HX soft starter is a new intelligent asynchronous motor starting and protection device. It is a motor terminal control equipment that integrates start, display, protection, and data collection. With fewer components, users can achieve more complex control functions.

The CMC-HX soft starter comes with a built-in current transformer, eliminating the need for an external one.


Mains voltage: AC380V±15%, AC690V±15%, AC1140V±15%

Power range: 7.5 ~ 630 kW, 15 ~ 700 kW, 22 ~ 995 kW

Applicable motor: Squirrel cage AC asynchronous(induction) motor

    • Features

    • ● SCR triggering close-loop control algorithm 
      The SCR close-loop control is specially designed for standard load and heavy load. User can choose current-limit start or voltage ramp start according to load conditions so as to realize absolutely smooth start without torque oscillation.

      ● Unique load application parameters 
      It is built-in 10 kinds of load types for users to choose. It provides a unique start control curve for each type of load to make soft start match the load, so as to achieve the best start and stop.

      ● Multiple start and stop modes 
      Voltage exponential curve start, voltage linear curve start, current exponential curve start, and current linear curve start. Programmable kick start torque and start current limit can be applied in each mode. According to the different loads, you can choose the corresponding start curve to achieve the appropriate starting effect. The device is provided with a variety of stop modes including programmable soft stop, free stop, braking, and pump stop. Unique basic algorithm makes the motor start and stop accurately and smoothly.

      ● Advanced communication function
      Standard Modbus RTU communication. Optional Ethernet/GPRS communication module makes user’s network connection control easier and improves the system's automation level and reliability.

      ● Analog signal control 
      Users can input 4-20mA or 0-20mA standard signal, and conduct upper and lower limit setting of analog to achieve the start and stop control of motor and alarm. The data (pressure, temperature, flow, etc.) can also be transmitted via a soft starter.

      4-20mA or 0-20mA standard analog signal output function.

      ● Fireproof material
      The product of below 90KW is in plastic structure made with inflaming retarding ABS material; for the product of 90KW and above, the upper cover is in plastic structure and main frame is made of aluminium-zinc plate with features of heatproof and corrosion resistance. 

      ● Movable panel
      The panel can be moved to equipment operating surface through machine interface for remote control.

      ● Powerful anti-interference property
      All external control signals are subject to optoelectronic isolation, and different anti-noise levels are set to adapt to the application in special industrial environments.

      ● Dual parameter function
      With two sets of basic parameters, it can control two motors with different power respectively.

      ● Self-adaption of power frequency 
      Self-adaption of power frequency 50/60 makes user easy to use.

      ● Dynamic fault memory 
      Up to 10 failures can be recorded, making it easy to find the cause of the malfunction.

      ● Perfect protective function 
      It detects current and load parameters, having overcurrent, overload, underload, overheating, phase failure, short circuit, three-phase current imbalance, phase sequence detection, frequency error and other functions.

      ● HMI
      LCD liquid crystal display panel; support English display.
    • Basic Parameters

    • Control power AC110V-10% to AC220V+15%, 50/60Hz
      Three-phase power Standard wiring AC380V / 690V / 1140V ±15% Internal delta wiring AC380V±15%
      Nominal current 18A~1200A, 23 rated values in total
      Applicable motor Squirrel cage AC asynchronous motor
      Start ramp mode Voltage exponential curve; Voltage linear curve; Current exponential curve; Current linear curve.
      Stop mode Free stop, Soft stop, Pump stop, Brake
      Logical input Impedance 1.8 KΩ, power supply +24V
      Start frequency Frequent or infrequent startup can be done, it is recommended that the number of startups per hour does not exceed 10 times
      Protective function Overcurrent, overload, underload, overheat, phase failure, three-phase current imbalance, phase sequence detection, overheat of motor and frequency error, etc.
      IP IP00
      Cooling type Natural cooling or forced air cooling
      Installation type Wall mounted
      Communication method RS485(Optional)
      Environmental condition When sea altitude is above 2,000m, soft starter should be derated for use. Ambient temperature: -25 ~ +45°C Relative humidity: less than 95% (20°C±5°C) Free of flammable, explosive and corrosive gas or conductive dust. Indoor installation, good ventilation, vibration less than 0.5G
       
    • Model Specifications

    • product-description1oci

      Adapted motor power

      (KW)

      Model of soft starter

      Rated current

      (A)

      Dimensions

      (mm)

      Net weight

      (kg)

      7.5

      CMC-008/3-HX

      18

      172*320*172

      4.3

      11

      CMC-011/3-HX

      24

      15

      CMC-015/3-HX

      30

      18.5

      CMC-018/3-HX

      39

      22

      CMC-022/3-HX

      45

      30

      CMC-030/3-HX

      60

      37

      CMC-037/3-HX

      76

      45

      CMC-045/3-HX

      90

      55

      CMC-055/3-HX

      110

      75

      CMC-075/3-HX

      150

      90

      CMC-090/3-HX

      180

      285*474*235

      18.5

      110

      CMC-110/3-HX

      218

      132

      CMC-132/3-HX

      260

      160

      CMC-160/3-HX

      320

      185

      CMC-185/3-HX

      370

      220

      CMC-220/3-HX

      440

      320*512*235

      23

      250

      CMC-250/3-HX

      500

      280

      CMC-280/3-HX

      560

      315

      CMC-315/3-HX

      630

      400

      CMC-400/3-HX

      780

      400*647*235

      40.8

      470

      CMC-470/3-HX

      920

      530

      CMC-530/3-HX

      1000

      630

      CMC-630/3-HX

      1200

    • Dimensions

    • Power range

      G

      H

      I

      K

      L

      M

      A

      B

      C

      Net weight

      (kg)

      Gross Weight

      (kg)

      7.5 ~ 75 kW

      172

      320

      172

      156

      240

      6

      20

      10

      100

      4.3

      4.7

      90 ~ 185 kW

      285

      474

      235

      230

      390

      9

      20

      10

      100

      18.5

      19.9

       220 ~ 315 kW

      320

      512

      235

      270

      415

      9

      20

      10

      100

      23

      25.8

      400 ~ 630 kW

      400

      647

      235

      330

      495

      9

      20

      10

      100

      40.8

      51.5

      •  product-description26nd
        75kW and below
      •  product-description3ej9
        90kW ~ 185kW
      •  product-description4q0c
        220kW ~ 315kW
      •  product-description5mld
        400kW ~ 530kW
    • Applications

    • ● Pumps and Fans;
      ● Conveyors and Belt Systems;
      ● Compressors;
      ● Centrifuges;
      ● Crushers and Mills;
      ● Mixers and Agitators;
      ● HVAC Systems;
      ● Conveyor Belt Systems;
      ● Mining Equipment;
      ● Water and Wastewater Treatment.
      Overall, low voltage soft starters are widely used in industrial processes where controlled acceleration and deceleration of electric motors are essential for efficient and reliable operation.